EasyLogic PM1130H Current, Voltage,Frequency,Power factor,Phase angle, RPM, Peak demand power, Harmonic distorsion (I THD & U THD), Active power,Active Energy, RS485, Class 0.5
Specifications |
Range of product | EasyLogic PM11XXH RS |
Country of Origin (Estimated) | India |
Warranty | 12 months |
CO/CQ | Yes (if) |
Product name & Device short name | PM1130H |
Product or component type | Dual source energy meter |
Power quality analysis | Total harmonic distortion |
Device application | Energy monitoring Main or redundant power monitoring |
Type of network | 2P 2P + N 3P 1P + N 3P + N |
Type of measurement | Current Voltage Frequency Power factor Phase angle RPM Peak demand power Harmonic distorsion (I THD & U THD) Active power Active energy |
Metering type | Unbalance current Power factor and displacement PF (signed, four quadrant) Reactive power Q, Q1, Q2, Q3 Average current Iavg Active, reactive, apparent energy (signed, two quadrant) Active power P, P1, P2, P3 Frequency Calculated neutral current Voltage U21, U32, U13, V1, V2, V3 Unbalance voltage Rotation speed Demand power P, Q, S Phase currents Apparent power S, S1, S2, S3 Phase current I1, I2, I3 RMS Average voltage Vavg |
Counter functions | ON-load source 1 hour counting ON hour counting ON-load source 2 hour counting Power interruption |
[Us] rated supply voltage | 48...277 V AC 45...65 Hz 48...277 V DC |
[In] rated current | 5 A 1 A |
Display type and colour | 7 segments LED and Red |
Display digits | 12 digit(s) - 14.2 mm in height |
Communication of data | Last cleared log Reading of measurements All counters Revolution speed Instantaneous and demand values |
Communication port protocol | Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V |
Communication port support | RS485 |
Measurement current | 5…6000 mA |
Signal | Voltage (impedance 5 MOhm)4 x Current 0.005...10 A (impedance 0.3 MOhm)6 x |
Measurement voltage | 35…480 V AC 50...60 Hz between phases 35…277 V AC 50...60 Hz between phase and neutral 277…999000 V AC 50...60 Hz with external VT |
Frequency measurement range | 45…65 Hz |
Number of outputs | 1 relay |
Measurement accuracy | Current +/- 0.5 % Voltage +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.01 Reactive power +/- 2 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Active energy +/- 0.5 % Apparent energy +/- 0.5 % Harmonic distorsion (I THD & U THD) +/- 5 % |
Accuracy class | Class 2 reactive energy conforming to IEC 62053-23 Class 0.5 active energy conforming to IEC 62053-22 |
Material | Polycarbonate |
Dimensions (mm) (H x W x D) | 96x96x52mm |
Cut-out dimensions | 92 x 92 mm |
Net weight | 300 GRM |