Circuit breaker, EasyPact CVS630F, 36kA at 415VAC, 600A, TM-D trip unit, 3P3d
Specifications LV563306 |
Range | EasyPact |
Country of Origin (Estimated) | India |
Warranty | 12 months |
CO/CQ | Yes (if) |
Product name & Device short name | Easypact CVS630F |
Device application | Distribution |
Poles description | 3P /4P |
Protected poles description | 3P 3d /4P 3d |
[In] rated current | 600 A at 40 °C |
Network type | AC |
[Ue] rated operational voltage | 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit rating | 600 A |
Thermal protection adjustment range | 420…600 A |
Long time pick-up adjustment range | 0.7...1 x In |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Connection pitch | 45 mm |
Breaking capacity [Icu] | 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability | 15000 cycles |
Electrical durability | 4000 cycles 415 V In conforming to IEC 60947-2 |
Protection type | Short-circuit protection (magnetic) Overload protection (thermal) |
Dimensions (mm) (W x H x D) | 3P/140x255x110mm 4P/185x255x110mm |
Net weight (Kg) | 3P/5.2Kg 4P/7.1Kg |
Front-panel Cutouts For toggle (X*Y) | 63x116mm |
Front-panel Cutouts (X*Y) For toggle with access to trip unit | 3P/143x184mm 4P/188x184mm |