Circuit breaker ComPacT NSX630H, 70kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d
Specifications |
Range | ComPacT NSX new generation |
Country of Origin (Estimated) | India |
Warranty | 12 months |
CO/CQ | Yes (if) |
Product name & Device short name | ComPacT NSX630H |
Device application | Distribution |
Poles description | 3P /4P |
Protected poles description | 3P 3d /4P 4d |
[In] rated current | 630 A at 40 °C |
Network type | AC /DC |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Trip unit name | MicroLogic 2.3 |
Trip unit technology | Electronic |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
Trip unit rating | 630 A |
[Ir] long-time protection pick-up adjustment range | 250...630 A |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
Connection pitch | 45 mm |
Breaking capacity [Icu] | 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability | 15,000 cycles |
Electrical durability | 4000 cycles at 440 V In |
Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
Dimensions (mm) (WxHxD) | 3P /140x255x110 mm 4P/185x255x110 mm |
Net weight (Kg) | 3P/6.2Kg 4P/8.13Kg |
Door cutout Dimensions (XxY) | 3P/127x127 mm 4P/127x127 mm |